Application:
Teck 90 cables are used in the pulp and paper, mining, petroleum, and chemical industries, as well as, in commercial and industrial building applications. They may be used under the following conditions:

Specifications:

TECK 90 Cables
ECI
Catalogue
Number
Conductors Ampacity
(Amps @30C)

Final O.D.
(inches)

Final O.D.
(mm)
Total
Weight
(lbs/1000 feet)
Total
Weight
(kg/km)
No. AWG
Size
T6XAAUS10-2C-BFT4-HL
2
10
30
0.81
20.7
308
459
T6XAAUS10-3C-BFT4-HL
3
10
30
0.84
21.3
358
532
T6XAAUS10-4C-BFT4-HL
4
10
24
0.91
23.2
437
651
T6XAAUS10-6C-BFT4-HL
6
10
24
1.01
25.7
556
827
T6XAAUS10-10C-BFT4-HL
10
10
21
1.29
32.8
902
1343
T6XAAUS10-15C-BFT4-HL
15
10
21
1.42
36.0
1162
1729
T6XAAUS10-20C-BFT4-HL
20
10
21
1.52
38.5
1410
2098
T6XAAUS12-2C-BFT4-HL
2
12
20
0.76
19.4
257
382
T6XAAUS12-3C-BFT4-HL
3
12
20
0.79
20.0
292
434
T6XAAUS12-4C-BFT4-HL
4
12
16
0.81
20.7
329
489
T6XAAUS12-5C-BFT4-HL
5
12
16
0.86
21.9
372
553
T6XAAUS12-6C-BFT4-HL
6
12
16
0.94
23.8
439
653
T6XAAUS12-7C-BFT4-HL
7
12
14
0.99
25.1
485
721
T6XAAUS12-8C-BFT4-HL
8
12
14
1.04
26.4
530
788
T6XAAUS12-10C-BFT4-HL
10
12
14
1.13
28.7
653
972
T6XAAUS12-15C-BFT4-HL
15
12
14
1.29
32.8
894
1331
T6XAAUS12-20C-BFT4-HL
20
12
14
1.39
35.4
1073
1597
T6XAAUS12-25C-BFT4-HL
25
12
14
1.48
37.6
1246
1855
T6XAAUS12-30C-BFT4-HL
30
12
12
1.57
39.8
1419
2112
T6XAAUS14-2C-BFT4-HL
2
14
15
0.71
18.1
223
332
T6XAAUS14-3C-BFT4-HL
3
14
15
0.74
18.8
249
371
T6XAAUS14-4C-BFT4-HL
4
14
12
0.76
19.4
277
412
T6XAAUS14-5C-BFT4-HL
5
14
12
0.81
20.7
310
462
T6XAAUS14-6C-BFT4-HL
6
14
12
0.86
21.9
345
513
T6XAAUS14-7C-BFT4-HL
7
14
10.5
0.91
23.2
396
590
T6XAAUS14-8C-BFT4-HL
8
14
10.5
0.96
24.5
432
643
T6XAAUS14-10C-BFT4-HL
10
14
10.5
1.01
25.7
487
725
T6XAAUS14-15C-BFT4-HL
15
14
10.5
1.16
29.4
666
991
T6XAAUS14-20C-BFT4-HL
20
14
10.5
1.29
32.8
852
1268
T6XAAUS14-25C-BFT4-HL
25
14
9
1.37
34.7
977
1454
T6XAAUS14-30C-BFT4-HL
30
14
9
1.44
36.6
1101
1639
COMPOSITE CONSTRUCTIONS
T6XAAUS14-3C-12-3C-BFT4-HL 3 14 12 0.89 22.6 369 551
3 12 16
T6XAAUS14-3C-10-3C-BFT4-HL 3 14 12 0.94 23.9 432 645
3 10 24
T6XAAUS14-3C-8-3C-BFT4-HL 3 14 12 1.07 27.18 608 907
3 8 36
T6XAAUS14-3C-6-3C-BFT4-HL 3 14 12 1.27 32.3 849 1267
3 6 52

Identification of Conductors:

  • 2 conductors: black, white
  • 3 conductors: black, red, blue
  • 4 conductors: black, red, blue, white
  • 5 or more conductors: black with alpha numeric code

CSA Certifications:

  • Standard C22.2 No. 38 "Thermoset Insulated"
  • Standard C22.2 No. 131 "Teck Cables"
  • Standard C22.2 No. 0.3 Clause 4.3.1 "Low Acid Gas"
  • Standard C22.2 No. 0.3 Clause 4.11.4 "Cables with FT4 Marking"
  • Standard C22.2 No. 239 Clause 6.2.4 "Outdoor Weathering"
  • Standard C22.2 No. 174 "Cables for use in Hazardous Locations"
    • Class I, Div. 1&2, Groups A,B,C,D
    • Class II, Div. 1&2, Groups E,F,G
    • Class III, Div. 1&2